TURN KEYSWITCH TO "MANUAL" - PRESS "SILENCE" TO STOP BEEPER.
TO ALERT A ZONE, PRESS DESIRED "ALERT" BUTTON. TO CANCEL PRESS AGAIN.
TO EVACUATE A ZONE, PRESS DESIRED "EVACUATE" BUTTON. TO CANCEL PRESS AGAIN.
TO SPEAK TO A ZONE, PRESS DESIRED ZONE "PA/SPEECH" BUTTON.
PICK UP MICROPHONE, OPERATE "PRESS-TO-TALK" BUTTON.
TO SELECT ALL ZONES, OR PREPROGRAMMED GROUP, PRESS DESIRED ALL ZONE OR
GROUP ZONE BUTTON. TO CANCEL PRESS AGAIN.
TO RESET LATCHED ALARMS AND FAULTS, PRESS "SILENCE" FOR 5 SECONDS.
TO ANSWER FIRE PHONE, LIFT HAND SET AND PRESS FLASHING "FIRE PHONE" BUTTON.
TO DISCONNECT, PRESS BUTTON AGAIN.
TO CALL A FIRE PHONE, LIFT HAND SET AND PRESS DESIRED "FIRE PHONE" BUTTON.
| Zone | State | FIP | BGA | Audio | BGA/FIP | W1 | W2 | W3 |
|---|
| Seq | Definition | Len |
|---|
| Signal | Standard | Pattern | Sequence |
|---|---|---|---|
| Evacuate | AS 2220.1 | Four tones, each rising 500 → 1200 Hz over 4 s, then the voice message. 16 s repeating sequence. | EA4 / EA6 |
| Evacuate | NZS 4512 | As AS 2220.1, with “Evacuate the building using the nearest fire exit” spoken twice. | EN1 / EN2 |
| Evacuate | ISO 8201 T3 / AS 1670.4 | 0.5 s on, 0.5 s off ×3 then 1.5 s off - each pulse sweeping 400 → 1200 Hz. “Emergency” in the first gap, “Evacuate Now” in the second. 8 s repeating sequence. | EA5 / EA7 |
| Evacuate | AS 4428.16:2020 | 520 Hz, T3 envelope, three groups, then “Emergency, Evacuate Now”. | EA1 / EA2 |
| Alert | AS 2220.1 / NZS 4512 | 420 Hz pulsed 625 ms on / 625 ms off, rising in volume through six levels after initial activation. Message every twelve pulses. | A1 / A2 |
| Alert | AS 4428.16:2020 | 520 Hz, 500 ms on / 3.5 s off, three pulses then the message. | AA1 / AA2 |
Visible warning lights supplementing the audible signal are amber for alert and red for evacuate under AS 2220; AS 1670.4 specifies no colours and uses the ISO 8201 T3 flash pattern. In manual mode the voice message is not included in the evacuate tone.
Alert tone is not used in Australia unless the building has a specific emergency plan requiring it. It remains the New Zealand default.
On a FIP or BGA alarm in zone N, after the Delay Before Action (normally zero):
Initial and Subsequent delays may not exceed 10 minutes for AS 2220 compliance, and may not exceed 42.5 minutes in any case. Delay Before Action should be zero unless the Evacuation Plan specifies otherwise. Switching Manual → Auto imposes a 5 second hold-off; power-up in Auto imposes 30 seconds before any cascade action.
NZS 4512:2003 brigade controls - Trial Alert sets all zones to Alert regardless of Auto/Manual. Trial Evacuate sets all zones to Evacuate and suspends cascading. Silence Alarms turns Alert and Evacuate off for all zones when in Auto, makes FIP inputs non-latching for 15 seconds after release, then restarts the cascade from the beginning.